Extended operation of the DC injection braking may cause the
motor to overheat!

Code

Parameter

Meaning

Acceptance

C036

0.0%
0.0...40%

Voltage for DC injection braking

ON-LINE

C107

999s
0.0...999s

Holding time for DC injection braking
999s = Holding time not limited

ON-LINE

With terminal control C048 serves as display whether the DC
injection braking is active or not.

With control via the keypad or the LECOM interfaces the DC
injection braking is (de-)activated via C048.

Code

Parameter

Meaning

Acceptance

C048

-0-
-1-

Deactivate DC injection braking
Activate DC injection braking

SH + PRG

For information about the automatic DC injection brake see
page 92.

5.2.4 JOG frequencies

If you need certain fixed settings as main set-value, you can call
programmed set-values via the JOG frequencies. These JOG
frequencies replace set-value 1. Please note that in configurations
with additional set-values, the set-value 2 is set to zero, as long as
a JOG frequency is active.

Programming of JOG frequencies
The JOG frequencies are set in two steps:

Select a JOG frequency under C038

Under C039, enter a value which you want to assign to the
selected JOG frequency

If you require several JOG frequencies, repeat the first two steps
correspondingly. The JOG frequencies must be entered as
absolute values. A maximum of 15 JOG frequencies can be
programmed.

Code

Parameter

Meaning

Acceptance

C38

-1-
-2-
-...-
-15-

JOG 1
JOG 2
JOG ...
JOG 15

SH + PRG

C39

-480...+480Hz

JOG frequency

ON-LINE