18

3.3

Application with medium overload,
peak torque up to 135% of the rated motor torque

−

For applications where only small starting and
overload torques are necessary (e.g. ventilators,
pumps).

−

The inverter provides 110% of the rated torque for
a maximum of 30s.
In the event of cyclic overload, the ratio of overload

time and cycle time must not exceed 0.1.

−

For this application, the monitoring of the output
current is set to operation with maximum power
using the codes C119 and C120 (see page 97)

−

Please note that a maximum ambient temperature
of 40°C is permissible.

Type

Order no.

Rated

motor

power

kW

Rated

output

current

A

max.

output

current

A for 30s

Output power

kVA

400V 50Hz 480V 60Hz

Mains

current

A

Power

loss

W

8601

33.8601_E

2.2

5.3

6.0

3.67

4.41

5.3

155

8602

33.8602_E

3.0

7.0

7.8

4.85

5.82

7.0

175

8603

33.8603_E

4.0

9.9

11.0

6.86

8.23

9.2

205

8604

33.8604_E

5.5

12.5

15.0

8.66

10.4

11.6

235

8605

33.8605_E

−

−

−

−

−

−

−

8606

33.8606_E

11.0

22.5

26.0

15.6

18.7

20.5

340

8607

33.8607_E

−

−

−

−

−

−

−

8608

33.8608_E

18.5

42.3

47.0

29.3

35.2

37.2

550

8609

33.8609_E

22.0

57.6

64.0

39.9

47.9

50.0

710

8610

33.8610_E

30.0

62.0

79.0

43.0

51.5

54.0

760

8611

33.8611_E

−

−

−

−

−

−

−

8612

33.8612_E

45.0

95.0

120.0

65.8

79.0

83.0

1110

8613

33.8613_E

55.0

115.0

150.0

79.7

59.6

100.0

1320

8614

33.8614_E

75.0

145.0

178.0

100.5

120.5

125.0

1640

90.0*

160.0*

178.0*

110.9*

133.0

138.0*

1640*

8615

33.8615_E

−

−

−

−

−

−

−

*

These data are valid for a maximum ambient temperature of 30°C.