18

3.3

Application with medium overload,
peak torque up to 135% of the rated motor torque

For applications where only small starting and
overload torques are necessary (e.g. ventilators,
pumps).

The inverter provides 110% of the rated torque for
a maximum of 30s.
In the event of cyclic overload, the ratio of overload

time and cycle time must not exceed 0.1.

For this application, the monitoring of the output
current is set to operation with maximum power
using the codes C119 and C120 (see page 97)

Please note that a maximum ambient temperature
of 40°C is permissible.

Type

Order no.

Rated

motor

power

kW

Rated

output

current

A

max.

output

current

A for 30s

Output power

kVA

400V 50Hz 480V 60Hz

Mains

current

A

Power

loss

W

8601

33.8601_E

2.2

5.3

6.0

3.67

4.41

5.3

155

8602

33.8602_E

3.0

7.0

7.8

4.85

5.82

7.0

175

8603

33.8603_E

4.0

9.9

11.0

6.86

8.23

9.2

205

8604

33.8604_E

5.5

12.5

15.0

8.66

10.4

11.6

235

8605

33.8605_E

8606

33.8606_E

11.0

22.5

26.0

15.6

18.7

20.5

340

8607

33.8607_E

8608

33.8608_E

18.5

42.3

47.0

29.3

35.2

37.2

550

8609

33.8609_E

22.0

57.6

64.0

39.9

47.9

50.0

710

8610

33.8610_E

30.0

62.0

79.0

43.0

51.5

54.0

760

8611

33.8611_E

8612

33.8612_E

45.0

95.0

120.0

65.8

79.0

83.0

1110

8613

33.8613_E

55.0

115.0

150.0

79.7

59.6

100.0

1320

8614

33.8614_E

75.0

145.0

178.0

100.5

120.5

125.0

1640

90.0*

160.0*

178.0*

110.9*

133.0

138.0*

1640*

8615

33.8615_E

*

These data are valid for a maximum ambient temperature of 30°C.