10 acceleration and deceleration times t, T = t f f - f – Lenze 8615E User Manual

Page 74

Advertising
background image

72

3.10

Acceleration and deceleration times T

ir

, T

if

The ramp generators (main set-value, set-value 2) are
programmed using the acceleration and deceleration times. Under
C012 and C013, the ramp generator for the main set-value (Set-
value 1/JOG frequency) receives its standard setting.

The acceleration and deceleration times refer to a change of the
field frequency from 0 to the maximum field frequency set under
C011. The times to be set are calculated as follows:

T = t

f

f

- f

ir

ir

dmax

d2

d1

T = t

f

f

- f

if

if

dmax

d2

d1

f /Hz

d

f

dmax
d2

f

fd1

0

tir

tif

Tir

Tif

t

Code

Parameter

Meaning

Acceptance

C012

5.0s
0.0...990s

Standard acceleration time for main set-
value

ON-LINE

C013

5.0s
0.0...990s

Standard deceleration time for main set-
value

ON-LINE

For programming and activation of additional acceleration and
deceleration times see page 81.

For ramp generator of set-value 2 see page 66.