5 additional acceleration and deceleration times – Lenze 8615E User Manual

Page 84

Advertising
background image

82

5.2.5 Additional acceleration and deceleration times

For the ramp generator of the main set-value (set-value 1/JOG
frequency) you can call additonal acceleration and deceleration
times from the memory, e.g. to change the acceleration speed of
the drive as from a certain speed.

Programming of additional acceleration and deceleration
times
The ramp times are set in two steps, under C100, one pair of
acceleration and deceleration times is selected.

Select an additional acceleration/deceleration time under C100

Set the desired acceleration time under C101 and the desired
deceleration time under C103.

If you need several additional ramp times, repeat the two steps
correspondingly.
To calculate the values to be entered, please observe the information
on page 72.

A maximum of 15 additional acceleration and deceleration times
can be programmed.

Code

Parameter

Meaning

Acceptance

C100

-1-
-2-
...
-15-

Additional pair of ramp times 1
Additional pair of ramp times 2
...
Additional pair of ramp times 15

SH + PRG

C101

0.0...990s

Acceleration time

ON-LINE

C103

0.0...990s

Deceleration time

ON-LINE

Assignment of the digital inputs
The number of required inputs for the function "Enable additional
acceleration/deceleration times" depends on the amount of the
required additional ramp times.

Number of required acceleration and deceleration

times

Number of required inputs

1

at least 1

2...3

at least 2

4...7

at least 3

8...15

4

A maximum of four inptus can be assigned to this function. For the
assignment of the inputs see the notes on page 78.

Advertising