4 motor voltage filter – Lenze 8615E User Manual

Page 47

Advertising
background image

45

6.4

Motor voltage filter

Advantages of using a motor supply filter:

•

Sinusoidal output voltages to supply electronic devices.

Please note:

•

Install the motor supply filter as close as possible to the inverter.

•

Select the control mode "V/f characteristic control"
(C006=-0-). The "magnetizing current control" form of control is
not permissible.

•

The chopping frequency must be set to 8 kHz (C018 = -4-).

•

The inverter is loaded additionally with approximately 10% of the
rated current of the motor supply filter.

•

The voltage drop across the motor supply filter at rated current
and rated frequency (f

d

= 50 Hz) is 7% of the inverter output

voltage.

•

The maximum permissible output frequency is 120 Hz.

•

With unscreened motor cables it should be tested whether the
system complies with the interference levels required for the CE-
EMC conformity.

Advertising