47

6.5

Cable protection

Cable protecting fuses for recommended cross-sections:

Inverter type

8601 - 03

8604, 05

8606, 07

8608, 09

Rated fuse current

16 A

20 A

35 A

50 A

Cable cross-section

2.5 mm

2

or

AWG 13 (12)

4 mm

2

or

AWG 11 (10)

10 mm

2

or

AWG 7 (6)

16 mm

2

or

AWG 5 (4)

Inverter type

8610, 11

8612

8613

8614

8615

Rated fuse current

63 A

100 A

125 A

160 A

200 A

Cable cross-section

25 mm

2

or

AWG 3

50 mm

2

or

AWG 0

50 mm

2

or

AWG 0

95 mm

2

or

AWG 3/0

95 mm

2

or

AWG 3/0

Replace defective fuses only with the specified type and when the
device is disconnected from the mains. All power terminals remain
live up to 3 minutes after mains disconnection!

Instead of cable protection fuses you can also use miniature circuit
breakers (e.g. Siemens type 5SX2, 3.. - 6)