5.2.10. Select parameter set, Load parameter set

You can store up to four different parameter sets, for example when
you want to process different material with one machine or if you want
to run different motors with one inverter.

Programming of parameter sets
To program several parameter sets, the following steps are
required:

Enter all settings for one application.

Select code C003 and save your parameter set for example
under -1- (parameter set 1).

Enter all settings for another application (e.g. different material).

Select code C003 and save your parameter set for example
under -2- (parameter set 2) etc.

Code

Parameter

Meaning

Acceptance

C003

-1-
-2-
-3-
-4-

Save parameter set 1
Save parameter set 2
Save parameter set 3
Save parameter set 4

SH + PRG

Load parameter set
After mains connection, parameter set 1 is loaded automatically. If
you want to change to other parameter sets using the digital
inputs, every parameter set must have at least one input with
"Select parameter set" and one input with "Load parameter set".
The number of inputs with the function "Select parameter set"
depends on the number of parameter sets which you want to use.

Number of additionally required parameter sets

Number of required inputs

1

2...3

at least 1

2

A maximum of two inputs can be assigned to this function. For the
assignment of the inputs see the notes on page 78.

A certain parameter set is loaded when you activate the inputs with
the function "Select parameter set" according to the table below
and then activate the input "Load parameter set" with the controller
inhibited.

The input with the smallest number is the first input, the input with
the next highest number is the second input, etc. (e.g. E1 = first
input, E2 = second input).

1st input

2nd input

Parameter set 1
Parameter set 2
Parameter set 3
Parameter set 4

0
1
0
1

0
0
1
1

Please only activate the input "Load parameter set" for a short time,
otherwise the selected parameter is loaded more than once.
The loading of the selected parameter set will be finished after
max. 0.5 seconds.
If all parameters are loaded, under C002 it is displayed which parameter
set was loaded.