10.3.5 Baud rate (LECOM1)

Under code C125 you can enter different baud rates.

Code

Parameter

Meaning

C125

-0-
-1-
-2-
-3-

9600 baud
4800 baud
2400 baud
1200 baud

10.3.6 History of reset faults

Under C161 to C168 you can read the last eight faults stored. The
last reset fault is displayed in C161.

10.3.7 Code bank (LECOM1)

With version 1.0 of the LECOM A/B protocol, codes up to C255 can
be processed. To reach also higher numbers with this version, the
accessible range can be changed by code C249. Code C249 exists
in every range.

Parameter in C249

Access to code range

-0-

C000...C255

-1-

C250...C505

-2-

C500...C755

-3-

C750...C1005

-4-

C1000...1255

-5-

C1250...C1505

-6-

C1500...C1755

-7-

C1750...C2000

Further information about serial communication with the standard
interface LECOM1 (LECOM-A/B), can be obtained from the
technical description LECOM-A/B, which we will be pleased to send
you on request.

10.3.8Enable automation interface (LECOM2)

If you want to integrate the inverter into complex automation
systems, you can connect an interface, e.g. Interbus-S or Profibus
or an automation module. Install the module and activate it under
C370.

Code

Parameter

Meaning

Acceptance

C370

-0-

-1-

no communication via automation interface
(LECOM2)
Communication via automation inteface
(LECOM2) is enabled

[SH + PRG]

If the communication via C370 is enabled but an automation
module is not connected, the inverter is inhibited.