6 description of the digital inputs and outputs – Lenze 8615E User Manual

Page 34

Advertising
background image

32

5.2.6 Description of the digital inputs and outputs

Digital inputs

Terminal

Use
(factory setting)

Signal for
activation

Programming see
page

20

Supply voltage 15V, 100mA

-

21

Remove quick stop, CW rotation

HIGH

58

22

Remove quick stop, CCW rotation

HIGH

58

28

Controller enable

HIGH

58

E1

Freely assignable input
(TRIP-set)

HIGH

78ff.

E2

Freely assignable input
(TRIP reset)

HIGH

78ff.

E3

Freely assignable input
(Activate DC injection braking)

HIGH

78ff.

E4, E5,
E6

Freely assignable input
(Enable JOG set-values, seven JOG values)

HIGH

78ff.

E7, E8

Freely assignable input
(Enable additional acceleration and deceleration
times, three ramp times)

HIGH

78ff.

Digital outputs

Terminal

Use
(factory setting)

Message

in the state

Programming see
page

"ready"

"Function
active"

41

Fault indication

TRIP

HIGH

LOW

88

44

Ready

RDY

HIGH

HIGH

88

45

Pulse inhibit

IMP

HIGH

LOW

88

A1

Freely assignable output
(Output frequency < Q

min

threshold)

LOW

LOW

86ff.

A2

Freely assignable output
(Maximum current reached - I

max

)

LOW

HIGH

86ff.

A3

Freely assignable output
(Set-value reached - RFG/O=I)

HIGH

HIGH

86ff.

Terminal

Switch
setting

Use
(factory setting)

Message

Programming see
page

A4

Frequency output
(6 times field frequency 6

f

d

Pulse train

Freely assignable output
(no function)

86ff.

39

Ground of the digital inputs and outputs
(external GND)

40

Internal ground (GND)

59

Supply input of the digital outputs (24V
ext. or 15V int.)

Advertising