3.7.2 I

0

control

"I

0

control" is especially suited for machines with a large

breakaway torque. Compared to the V/f characteristic control it
provides considerably larger torques up to the motor rated point.
The advantages of I

0

control can be used especially for single

drives. It is also possible for group drives, provided that the motors
are of the same type and have the same load, e.g. two identical
drives, which drive a common shaft from two sides.

V/f rated frequency
To program the I

0

control, the I

0

set-value and the correct V/f rated

frequency must be set for the motor(s) (see page 68).

I

0

set-value

You can determine the I

0

set-value using the cos

ϕ

, the rated motor

current and the following diagram.

0.70

0.75

0.80

0.85

0.90

0.95

1.00

0.25

0.30

0.35

0.40

0.45

0.50

0.55

0.43

K

cos

Example:

cos

ϕ

= 0.85

K = 0.43

I - set - value = K I

0

N

motor

Enter the calculated value under C020. For group drives, multiply
the calculated value with the number of motors.

Code

Parameter

Meaning

Acceptance

C015

50.0Hz
7.5...960Hz

V/f rated frequency

ON-LINE

C020

0.0...0.5A

I

max inverter

I

0

set-value

ON-LINE

Advertising