2.1.1 Parameter setting by two codes

Some parameters are set by two codes. A preselection code is
used to select the parameter which is to be changed. The
parameter is then changed by another code. For example, to set
the JOG frequency JOG3, first set the preselection code C038 to
-3- and then set the desired frequency for JOG3 via code C039.

2.2

Save parameters

After the acceptance, new parameters are saved in the RAM until
the inverter is connected to mains voltage.

If you want to permanently save your settings, process as follows:

Select code C003.

Select -1-, i.e. parameter set 1.

First press SH and then in addition PRG. The display shows
--ok--.

Now you can disconnect the inverter from the mains. Your settings
are saved permanently under "parameter set 1".
To save different parameter sets see page 85.

2.3

Load parameters

If you only need one parameter set, you permanently save your
changes under parameter set 1. After every mains connection,
parameter set 1 is loaded automatically. To load different
parameter sets, see page 85.