3.8

Minimum field frequency f

dmin

You can use code C010 to program a minimum output frequency.
This changes the influence of the analog set-value to set-value 1 in
the factory-set configuration C005 = -0- (not for other
configurations).

analog set-value
X1/term. 8

100%

set-value 1

0

dmax

f

dmin

f

For set-value inputs via keypad or LECOM interfaces, the f

dmin

setting is not effective.

Code

Parameter

Meaning

Acceptance

C010

0.0Hz
0.0...480Hz

minimum field frequency

ON-LINE

3.9

Maximum field frequency f

dmax

Via C011, you can select a maximum field frequency between 7.5
and 480 Hz. The value will be a reference for the analog and
scaled set-value input and for the acceleration and deceleration
times. For absolute set-value input, e.g. via keypad or JOG
frequencies, f

dmax

is the limit value.

With a configuration with PI controller (C005 = -10-...-15-), the
output frequency can be up to 200% f

dmax

.

When you want to change the maximum field frequency in large
increments via the LECOM interfaces, first inhibit the controller.

Code

Parameter

Meaning

Acceptance

C011

50.0Hz
7.5...480 Hz

maximum field frequency

ON-LINE