Assignment of the digital inputs
The number of required inputs for the function "Enable JOG
frequency" depends on the amount of the required JOG
frequencies.
JOG frequencies

Number of required JOG

frequencies

Number of required inputs

1

at least 1

2...3

at least 2

4...7

at least 3

8...15

4

A maximum of four inputs can be assigned to this function. For the
assignment of the inputs see the notes on page 78.

Enabling JOG frequencies
With terminal control
activate the assigned digital inputs
according to the table below.
The input with the smallest number is the first input, the input with
the next highest number is the second input, etc.
(e.g. E4 = first input, E5 = second input).

1st input

2nd input

3rd input

4th input

JOG 1

1

0

0

0

JOG 2

0

1

0

0

JOG 3

1

1

0

0

JOG 4

0

0

1

0

JOG 5

1

0

1

0

JOG 6

0

1

1

0

JOG 7

1

1

1

0

JOG 8

0

0

0

1

JOG 9

1

0

0

1

JOG 10

0

1

0

1

JOG 11

1

1

0

1

JOG 12

0

0

1

1

JOG 13

1

0

1

1

JOG 14

0

1

1

1

JOG 15

1

1

1

1

With terminal control, the active JOG frequency is displayed under
C045.

With control via keypad or LECOM interfaces C045 is used to
activate the JOG frequencies.

Code

Parameter

Meaning

Acceptance

C045

-0-
-1-
-2-
-...-
-15-

Activate set-value 1
Activate JOG 1
Activate JOG 2
Activate JOG ...
Activate JOG 15

SH + PRG