Lenze EDB9300UES User Manual

Page 121

Advertising
background image

Operation and Software

116

BA8230

Zero zone additional demand

This demand forms part of a characteristics formation device on the additional
demand channel.
With unipolar demands it determines the range in which the analog demand read in
from terminal :29/:30 is limited to “Min. additional demand”.
With bipolar demands (-10 V ... +10 V) it defines the zero zone.

Adjustment range:

0 % ... 20 %

As supplied:

0.5 %

Main + additional demand

This parameter allows you to add an additional demand to the main (speed) demand.
As standard, the additional demand is the analog demand from terminal :29/:30.

Select list:

- No
- :27/:28 + :29/:30

As supplied:

No

4-20mA monitor

This parameter determines the response on detection of a wire break. The monitors
for the analog demands at terminals :27/:28 and :29/:30 are active if they were
selected as 4-20mA (line current) demand sources.

Select list:

- Warning
- Shut down

As supplied:

Shut down

Response:

- Warning:

Wire break detection generates a warning message in the event log. A signal can be
output to terminals :23/:24 through the selector switch “D-Output 1 :”23/:24”.

- Shut down:

If this is selected, a wire break causes the 8230 frequency inverter to be shut down
and creates a corresponding entry in the error log. The 8230 frequency inverter can
only be switched on again when the error is acknowledged.