Operation and Software

118

BA8230

A-Output 2 terminal 35

This parameter determines which control variable is to be output as an analog value
at the monitor output (D/A output) terminal :35 (AA1). Digital resolution is 12 bit, the
range of values at the analog output is -10 V ... +10 V.
Privided that Scal. A-Output 2 = 100 % the following apply according to the selction
list:

- Output frequency

f = rated frequency
(The rated frequency as supplied is 100 Hz.
At an output frequency of 50 Hz the output voltage is
5 V. In the negative direction also the output voltage
becomes negative).

- Speed

Output:

frequency

rated

on

Speed

Speed

V

10

*

eg. 5 V: Synchronous speed at 50 Hz.
In the negative direction also the output voltage is
negative.

- Motor current

Output 10 V, if the r.m.s. value of the fundamental wave of
the motor current is equal to the maximum maximum
controller current.

- Motor voltage

Output 10 V, if the r.m.s. value of the fundamental wave of
the motor voltage is equal to the rated mains voltage

.

- Torque

10 V with rated torque of the parameterized motor.

- Motor power

10 V with rated power of the parameterized motor.

- Link voltage

Output 10 V, if the link voltage is equal to the rectification
value of the rated mains voltage.

- Variable 2 = XIM

100 % magnetising current based on the rated current
of the unit.

As supplied:

Motor current

Scaling A-Output 2

This parameter is used for scaling the D/A output at terminal :35. It represents the
reference value which produces a 10 V output.

Adjustment range:

0 ... 200 %

As supplied.

100 %