Technical Data
40
BA8230
Fig. 16: Encoder interface - indicators, selector switches, connectors
The input and output signals for the encoder interface are connected through the
plug-in terminal strip X10. Connection to the A10 control board is by means of ribbon
cables.
Technical data of inputs and outputs
Inputs (incremental encoder)
1 encoder input
Configuration:
2 differential inputs, separate potential,
for 2 incremental encoder tracks offset
through 90°
1 differential input, separate potential, for
the zero pulse track (not essential)
Input voltage level:
+5 V/+15 V/+24 V adjustable
Input frequency of track signals:
Max. 1 MHz
Loading per Differential input
≤
35 mA
Dimensions (width x heigth):
168 mm x 120 mm
Weight:
ca. 0.35 kg