Transport, Installation and Connection

BA8230

71

Note:

The cable cross-sections stated in Table 23 can only be considered general
guidelines. The cable dimensions must satisfy the regulations and any works
standards applicable at the installation.

8230 frequency inverter

Type

Mains connection

Motor connection

Screw connection

Motor + Mains connection

Recommended

copper cable

cross-sections

Applicable

overload

protection NH

fuse

Recommended

copper cable

cross-sections

Steel screw

Strength class 8.8,

not greased

Tightening
torque

Max. direct

single

connection

cross-section

at the unit

[mm²]

[mm²]

[Nm]

[mm²]

8231

2 x 3 x 95

315 A

2 x 3 x 95

M12

92

200

8232

2 x 3 x 120

355 A

2 x 3 x 120

M12

92

200

8233

2 x 3 x 150

400 A

2 x 3 x 150

M12

92

200

8234

2 x 3 x 185

500 A

2 x 3 x 185

M12

92

200

Table 23: Cable connections

Note concerning motor connection

The following main factors must be taken into consideration for connecting motors to
the 8230 frequency inverter:

8230 frequency inverter unit type: As standard the response threshold for earth

fault

detection on the motor side is 10 % I

N

.

8230 frequency inverter pulse frequency

Motor insulation system: Details from the motor manufacturer concerning the max.
motor voltage/current in the motor terminal box, suitability for inverter operation

Cable type: Screened, with armouring or without screen

Effective cable length: Parallel cables, group supply

Cable cross-section: Voltage drop

1.75 % or

3 %

Suitable screened heavy current cable 0.6/1 kV

Cross-section [mm

2

]

Type

Manufacturer

to 25

Ölfex-Servo - 730 CY

Lappkabel

10 ... 120

Protoflex-EMV-CY
2YSLCY-J

Siemens

10 ... 185

NYCWY 3x XX/Y
(für Y jeweils größter Wert)

Normkabel