Lenze EDB9300UES User Manual
Page 40
![background image](/manuals/566237/40/background.png)
Technical Data
BA8230
35
A common output choke at the inverter output is generally to be provided in multiple
motor applications.
frequency inverter
Motor choke
Motor choke
type
with medium overload
with high overload
8231
ELD3-0040H260
ELD3-0050H220
8232
ELD3-0030H330
ELD3-0040H260
8233
ELD3-0025H400
ELD3-0030H330
8234
ELD3-0020H500
ELD3-0025H400
Table 17: Output chokes for 8230 frequency inverter
Characteristics
Iron core choke
3-leg configuration optimised for inverter operation
Operating voltage
400 V ... 460 V
Operating frequency
max. 150 Hz
Ferrite core output chokes for higher
frequencies by request
Protection class
IP 00
Mode of operation
DB
Environment class
DIN EN 60721 Part 3-3 3K3 / 3M2 / 3C2 / 2K2
Important!
8230 frequency inverter motor filters are designed for a maximum
pulse frequency of 3 kHz.
See section 3.5 for further information.
See section 2.8.10 for dimensions, weights and losses.
Show/Hide Bookmarks