Technical Data

BA8230

55

Terminal :8

FAST STOP

Fast Stop function by a flank from HIGH to LOW.
The drive runs to zero at the parameter-adjustable “ramp fast stop”.
The pulses are then disabled and the internal DC main contactor is
de-energised. If the optional brake chopper with braking resistor is
connected, the link is force-discharged after approx. 30 s.

Terminal :9

LEFT

Left, demand enable on HIGH
If “demand preset 0 ... +10 V" or “line current” is preset, operation
in the left direction is enabled with a HIGH signal at terminal :9.
Negative values at the demand input produce a demand of zero.
If neither LEFT nor RIGHT is HIGH, no direction is enabled. If both
LEFT and RIGHT are HIGH, the signal set first takes priority.

Terminal :10

DISABLE

Inverter disable
This disables the pulses on LOW and de-energises the internal DC
main contactor. If the optional brake chopper with braking resistor
is connected, the link is force-discharged after approx. 30 s.


Terminal :11

RIGHT

Right, demand enable on HIGH
If “demand preset 0 ... +10 V" or "line current” is preset, the right
direction is enabled on a HIGH signal at terminal :11. Negative
values at the demand input result in a demand of zero.
If neither LEFT nor RIGHT is HIGH, no direction is enabled.
If both LEFT and RIGHT are HIGH, the signal set first takes priority.

Terminal :12

EXTERNAL ERROR

Opening the external error contact causes the inverter to be
disabled and de-energises the DC contactor. The motor idles down.
Restarting is only possible after an acknowledgement.

Terminal :13

ERROR RESET

Acknowledgement of an error
A change in level from LOW to HIGH is an acknowledgement.

Terminal :14

D-INPUT 1

Digital input 1
Function parameter-adjustable (05 Digital I/O

Terminal :14)

Standard setting:

- Motor potentiometer higher

Alternatively:

- Select fixed speed.1

Input resistance: 4.8 k