2.4.1.2 Mains chokes

Mains choke is required in the supply cable to reduce the harmonics and

(3-phase chokes)

limit commutation failures. The mains chokes for the relevant 8230 frequency inverter
types are listed in the table below.

Mains chokes are not included in the 8230 frequency inverter.

The mains choke must be allocated individually to each 8230 frequency inverter to
guarantee decoupling when several units are operated at the same mains supply
point. A mains choke of high rating is not suitable for several low power 8230
frequency inverter units.
Mains chokes improve the overvoltage protection. The impedance of the choke forms
a voltage divider with the impedance on the mains side. When the choke is not
saturated magnetically it limits the current rise when the voltage rises. This prevents
excessive overvoltages at the 8230 frequency inverter mains input.

frequency inverter

Mains choke

Mains choke

type

with medium overload

with high overload

8231

ELN3-0011H270

ELN3-0014H200

8232

ELN3-0011H270

ELN3-0011H270

8233

ELN3-0009H370

ELN3-0009H300

8234

ELN3-0006H450

ELN3-0009H370

Table 9: Mains chokes

Characteristics

Relative short circuit voltage

u

K

= 3.8 %

(400 V supply voltage, rated output current)

Operating voltage

380 V ... 460 V +10/-15 %, 50/60 Hz ±5 %

Protection class

IP 00

Mode DB
Environment class

DIN EN 60721 Part 3-3 3K3 / 3M2 / 3C2 / 2K2

See section 2.8.2 for dimensions, weights and installation instructions