Lenze EDB9300UES User Manual

Page 23

Advertising
background image

Technical Data

18

BA8230

EMC interference resistance IEC1800-3/prEN61800-3 (IEC224/21CDV); EN50082-2

The following limits for interference resistance are fulfilled when a mains choke and
screened control cables are used.

Requirement

Standard

Severity level

ESD

(Static discharge)

IEC1000-4-2 (IEC 801-2) Air discharge (AD)

±

8 kV

Contact discharge (CD)

±

6 kV

Burst
(Transients)

IEC1000-4-4 (IEC 801-4) Mains connection

2 kV, 5 kHz

kap

Load connection

2 kV, 5 kHz

kap

Demand

2 kV, 5 kHz

kap

General interfaces

2 kV, 5 kHz

kap

Surge
(Surge voltages)

IEC 801-5

Mains/load connection
1,2 / 50 µs phase - PE

2 kV

1,2 / 50 µs phase - phase

2 kV

Limit curves, radio interference voltage

Fig. 7: Limit curves (QPK-Quasi Peak) radio interference voltage

Fig. 8: Typical interference voltage characteristic at mains input

Fig. 8 shows the typical interference voltage characteristic at the mains input in the
example of the 8230 frequency inverter. Differences are possible according to the
connection configuration and unit involved.