Operation and Software

BA8230

121

D-Output1 23/24

This parameter determines which digital monitoring signal is output at
terminals :23/:24. The signal has a decay delay of 200 ms. The signal to be output
can be inverted through the parameter “Invert D-Output 1”.

Select list:

- Speed reached
- Speed = zero
- Speed > Ref. speed
- Load current > Il-Ref
- Warning

As supplied:

Speed reached.

If “Warning” is selected, the temperature warning is output as well as the wire break
monitor for the 4-20 mA demand sources if selected.
See “Window speed reached”, “Window speed = 0”, “Reference speed” and
“Reference load current” for setting the comparison values and tolerances for the
above monitors.

Invert:23/24

This parameter allows you invert the signal output at terminal :23/:24.

Select list:

- Yes
- No

As supplied:

No

Window speed reached

This parameter determines the band of tolerances within which the system detects
that the drive is running at the specified speed.
The signal can be output through the field bus and, if configured accordingly,
through :23/:24 (see parameter “D-Output 1 23/24”).
If there is a change in the ratio between "Standard frequency" and "No. of pairs of
poles", the parameter setting is affected in proportion.

Adjustment range:

(0.001 ... 0.1) * "Standard frequency" * 60/No. of pairs of
poles

As supplied:

25 min

-1