7 connection, terminal wiring, 1 power stack, 1 3ac supply – Lenze EDB9300UES User Manual

Page 50: Connection, terminal wiring, Power, Stack, Supply

Advertising
background image

Technical Data

BA8230

45

2.7 Connection, terminal wiring

2.7.1 Power stack

The power stack consists of a B6 diode input bridge, charging circuit, link and inverter.

The AC bridge connections U1, V1, W1 are connected to the 3-phase AC supply
network L1, L2, and L3.

2.7.1.1 3AC supply

Connections at top

Function

PE

Earth terminal

L1

L2

Mains supply 3AC 400 ... 460 V

L3

-

Not used

RB1

Braking resistor

+UG

(+UG = link plus)

Connections at foot

Function

PE

Earth terminal

U1

V1

Motor connection

W1

+UG

Link plus

-UG

Link minus

PE

Earth terminal

Fig. 18 shows the 8230 frequency inverter power connections for a 3AC supply. The
8230 frequency inverter supply components marked * are not essential.


Note:

In exceptional cases it can be necessary to reverse the order of components 1), see

Fig. 18. This is the case, for example, if additional auxiliary supplies such as external
motor fans are to be operated at the feed point or function earthing is not consistent.


}

}

}

Show/Hide Bookmarks

Advertising