4 fuse circuit breakers, 5 mains contactor, Fuse circuit breakers – Lenze EDB9300UES User Manual

Page 28: Mains contactor

Advertising
background image

Technical Data

BA8230

23

2.4.1.3 Line fuses for

Installation instructions for a 3AC 8230 frequency inverter connection in the

operation class gL and

customer’s low voltage distribution system:

cable cross-sections

The NH fuses recommended for operation class gL and the cable cross-sections to be
used for 8230 frequency inverter 3AC mains connections are shown in the following
table. Minimum cross-sections for mains supplies cables with PVC insulation
according to EN 60204-1:1992 are given for an ambient temperature of

ϑ

= 40 °C and

laying method E.

8230 frequency inverter
type

Unit output current

Recommended fuse
gL characteristics

Recommended cable
cross-sections for PVC
insulated copper cable

1.2 x Rated
current

1.5 x Rated
current

Max. current
for 60 s

Type

3-phase cables
NYY/ NYM

[A]

[A]

[A]

8231

257

216

324

315 A Gr.2

2x3x95 mm²

8232

304

257

365

355 A Gr.2

2x3x120 mm²

8233

396

325

488

400 A Gr.2

2x3x150 mm²

8234

483

400

600

500 A Gr.3

2x3x185 mm²

Table 10: 8230 frequency inverter AC line fuses

2.4.1.4 Fuse circuit breakers

The above semiconductor fuses (aR-Characteristics) with 100 mm length to
DIN 43 653 can be installed as an alternative to fuse bases in conjunction with the
hand-operated fuse circuit breaker.
This creates a separation point in the 3AC mains supply and all poles of the
semiconductor fuses can be switched.

2.4.1.5 Mains contactor

Contactors 3 AC 400 V, 50/60 Hz
On 3AC mains supplies which include (automatic) on/off switching of the mains
voltage at the 8230 frequency inverter input (eg. 8230 frequency inverter units with
optional brake chopper and braking resistor), 3-phase contactors according to the
following tables are used.

Important! Note the mains contactor control voltage!

8230 frequency
inverter type

Unit output current

Contactors 3 AC

1.2 x Rated
current

1.5 x Rated
current

Max. current
for 60 s

Type

[A]

[A]

[A]

8231

257

216

324

LS247.22

8232

304

257

365

LS247.22

8233

396

325

488

CA-5-550A

8234

483

400

600

CA-5-550A

Table 11: Mains contactors

Mains contactors and accessories are stated for 400 V, 50/60 Hz mains voltage.