Lenze EDB9300UES User Manual

Page 122

Advertising
background image

Operation and Software

BA8230

117

A-Output 1 terminal 33

This parameter determines which control variable is to be output as an analog signal
at the monitor output (D/A output) terminal :33 (AA1). Digital resolution is 12 bit, the
range of values at the analog output is -10 V ... +10 V.
Privided that Scal. A-Output 1 = 100 % the following apply according to the selction
list:

- Output frequency

f = standard frequency
(The standard frequency as supplied is 100 Hz.
At an output frequency of 50 Hz the voltage output is
5 V. In the negative direction also the output voltage
is negative).

- Speed

Output:

frequency

rated

on

Speed

Speed

V

10

eg. 5 V: Synchronous speed at 50 Hz.
In the negative direction also the output voltage is
negative.

- Motor current

Output 10 V, if the r.m.s. value of the fundamental wave of
the motor current is equal to the maximum maximum
controller current.

- Motor voltage

Output 10 V, if the r.m.s. value of the fundamental wave of
the motor voltage is equal to the rated mains voltage

.

- Torque

10 V with rated torque of the parameterized motor.

- Motor power

10 V with rated power of the parameterized motor.

- Link voltage

Output 10 V, if the link voltage is equal to the rectification
value of the rated mains voltage.

- Variable 1 = XIL

100 % torque-forming component of motor current
based on unit rated current.

As supplied:

Output frequency

Scaling, A-Output 1

This parameter serves to scale the D/A output at terminal :33. It represents the
reference value which produces a 10 V output.

Adjustment range:

0 ... 200 %

As supplied:

100 %