Technical Data

32

BA8230

Application range of motor filters:

With mains supply voltages U

N

460 V standard motors or motors with equivalent

insulation characteristics can be used on 8230 frequency inverter. Standard
motors of 400 V ... 460 V are designed for the voltage rates of rise and fall and
voltage peaks of up to 1300 V which occur during inverter operation. If other
makes of motors are used, please contact the motor supplier concerning suitability
for inverter operation. 8230 frequency inverter motor filters are to be used if the
insulation resistance of the motors and the maximum permitted voltage in the
motor terminal box does not match the required value of 1300 V and the permitted
voltage rate of rise in the winding insulation is <3 kV/µs.
If the motors do not satisfy these requirements, 8230 frequency inverter motor
filters or application-dependent output chokes are to be used.

With long parallel runs of unscreened motor cables in industrial applications a

motor filter is recommended to reduce the effect of adjacent cable runs caused by
direct magnetic coupling.

Radiated interference, particularly for high frequency components in the motor

current, is reduced by limiting the voltage rate of rise when using motor cables
which are not screened.

frequency inverter

Motor filters

Motor filters

type

with medium overload

with high overload

8231

ELM3-0040H260

ELM3-0050H220

8232

ELM3-0030H330

ELM3-0040H260

8233

ELM3-0025H400

ELM3-0030H330

8234

ELM3-0020H500

ELM3-0025H400

Table 16: motor filters

See section 2.8.8 and 2.8.9 for dimensions, weights and power losses.

Note:

See section 3.5 “Mains and motor connection” for further information and the
maximum permitted motor cable length when using filters.