Transport, Installation and Connection

72

BA8230

The recommended guidelines for copper cable cross-sections guarantee a voltage
drop of <3 % up to conductor temperatures of 50 °C. The values stated apply to a
400 V supply at rated current for frame size 1 up to approx. 80 m and for frame sizes
2, 3 and 4 up to approx. 160 m.

The maximum permitted cable lengths for connecting 3-phase asynchronous motors
to the 8230 frequency inverter are stated in

Table 24

.



Max. permissable motor cable lengths of the 8230 frequency inverter

8230 frequency inverter
Type

Max. suitable motor cable lengths, 8230 frequency inverter

Unscreened cable NYY/NYM

1)

Screened cable NYCWY

1)

no circuit

2)

with motor

choke

2) 4)

with motor

filter

3)

U

N

=400 V

f

p

=3 kHz

with motor

filter

3)

U

N

=460 V

f

p

=3 kHz

No circuit

2)

with motor

choke

2

with motor

filter

3)

U

N

=400 V

f

p

=3 kHz

with motor

filter

3)

U

N

=460 V

f

p

=3 kHz

[m]

[m]

[m]

[m]

[m]

[m]

[m]

[m]

8231

300

400

400

300

250

350

300

200

150

5)

120

5)

200

5)

150

5)

8232

300

450

450

350

250

350

350

250

150

5)

120

5)

200

5)

150

5)

8233

300

450

450

350

250

350

350

250

150

5)

120

5)

200

5)

150

5)

8234

300

450

450

350

250

350

350

250

150

5)

120

5)

200

5)

150

5)

Table 24: Max. permitted motor cable lengths