1 terminal strip wiring: x15 and signal functions, Terminal strip wiring :x15 and signal functions – Lenze EDB9300UES User Manual

Page 54

Advertising
background image

Technical Data

BA8230

49

2.7.2.1 Terminal strip wiring :X15
and signal functions

Terminal :X15

Function

Comments

1)

:1

DC +24 V

Max. load: 800 mA

:2

DC 0 V

Reference potential for DC +24 V

:3

PTC-

Motor thermistor connection

:4

Motor temperature

Motor thermistor connection

Binary inputs

:5

ON / STOP

Flank LOW

HIGH = ON

:6

MANUAL/AUTOMATIC

+24 V = Automatic; Open = Manual

:7

STOP

Flank HIGH

LOW = STOP

:8

FAST STOP

Open = Fast Stop

:9

LEFT

+24 V = Left

:10

INHIBIT

Open = Inhibit, drive idles down

:11

RIGHT

+24 V = Right

:12

EXTERNAL ERROR

Open = Inverter disabled

:13

QUIT

Flank LOW ® HIGH = acknowledge

:14

DIGITAL INPUT 1

Function available

:15

DIGITAL INPUT 2

Function available

:16

DIGITAL INPUT 3

Function available

Binary outputs

:17

Relay

DC 30 V; 0,5 A max.

:18

contact

closed on "READY"

2)

:19

Relay

DC 30 V; 0,5 A max.

:20

contact

closed on "ON"

:21

Relay

DC 30 V; 0,5 A max.

:22

contact

2)

closed on "ERROR"

3)

:23

Relay

DC 30 V; 0,5 A max.

:24

contact

2)

Function available

Standard: "SPEED REACHED"

3),4)

:25

DC +24 V

parallel to terminal 1

:26

DC 0 V

parallel to terminal 2

Demand inputs

Analog outputs

:27

MAIN DEMAND (-)

Differential input

:28

MAIN DEMAND (+)

Differential input

:29

ADDIT. DEMAND (-)

Differential input

:30

ADDIT. DEMAND (+)

Differential input

:31

DC +10 V

Rating: 20 mA resistant to short
circuit

:32

DC -10 V

Rating: 20 mA resistant to short
circuit

:33

A-OUTPUT 1

Rating: 3 mA

:34

DC 0 V

Reference potential 0 V for DC + 10 V

:35

A-OUTPUT 2

Rating: 3 mA

:36

DC 0 V A-OUTPUT

Reference potential 0 V Analog outp.

A-OUTPUT 1, A-OUTPUT 2


1)

As supplied: Terminals :7, :8, :10, :11, :12 are connected to +24 V (terminal :1).
Terminals :3 and :4 are bridged. The 8230 frequency inverter can therefore be
controlled directly via the control unit.

2)

The function can be re-directed with the PC handling software if required

3)

The function can be inverted if required

4)

The output can be adjusted.

READY

ON

ERROR

SPEED

REACHED