Transport, Installation and Connection

74

BA8230

Cross-section

Resistance R

50

Inductive reactive resistance

[mm²]

[

/km]

[

/km]

95

0.216

0.0754

120

0.171

0.0733

150

0.139

0.0733

185

0.110

0.0725

Table 25: Operating values for PVC insulated cable at 50 °C cable temperature.


To compensate for internal voltage drops 8230 frequency inverter units can simulate
the output voltage in an over-modular manner. The voltage drop across the motor
cable however cannot be compensated without direct measurement at the motor
connection. However the motor current consumed increases almost proportionally
through a reduced motor voltage at the same torque and increases the motor losses
for a squared reduction in motor trip torque and a reduction in motor flux.

If the values for the voltage drop are exceeded, 3-phase asynchronous motors with
U

Motor

< U

Mains

are to be used. If standard 3-phase motors are used, a reduction in the

type point can be made to determine the revised rating point.

Example:

50 Hz / 400 V changed to 47.5 Hz / 380 V

The level of interference on the mains side which is associated with the power is
increased through longer motor cables. A mains filter is recommended if sensitive
consumers are operated on the same mains supply and motor cable lengths
exceed 50 m.