Technical Data
58
BA8230
2.8 Dimensions,
Installation drawing, weights
2.8.1 8230 frequency inverter build-in units
Fig. 28: Dimensions, 8230 frequency inverter build-in units
The clearances above, below and to the side must be provided. The mains choke
may not be installed directly under the unit.
8230 frequency
inverter type
Frame size
Enclosure dimensions
Weight
Installation clearances
(Clearance for cooling air inlets)
Width B
Depth T
1)
Height H
top o
bottom u
at side s
[mm]
[mm]
[mm]
[kg]
[mm]
[mm]
[mm]
8231
8
495
419
1049
90
300
200
0
8232
8A
495
419
1225
90
300
200
0
8233
9
495
419
1499
140
300
200
0
8234
9A
495
419
1675
140
300
200
0
1)
The unit depth can be reduced by 19 mm by removing the decorative facia on the
door.
Table 18: Dimensions, weights, installation clearances