Example:

With a 10 % duty cycle the resistor may be switched on continuously for a maximum
of 15 seconds. Also permissible, for example, would be 5 seconds on and 45 seconds
off. A load cycle with 20 seconds on and then 180 seconds off would not be
permissible.

Technical data of braking resistors:

Type ERBD015R04K0

0.4 kW / 15

Resistance

15

Peak load

40 kW

Duty cycle % / 150 s

10 %

Max. rating

600 kWs

Continuous capacity

ϑ

= 45 °C

4 kW

Continuous current at DC 750 V

16 A

Peak current at DC 750 V

50 A

Permitted ambient temperature

-25 ... +45 °C

max. 55 °C: Power reduction of 1 % / 1 °C

Protection class

IP 20

Table 13: Technical data of braking resistors

8230 frequency
inverter

Assignment of braking resistors

Number of

parallel

resistors

Total

resis-

tance

Total continuous

power

Total continuous

current

Total peak

power

Total peak

current

[Ohm]

[kW]

[A]

[kW]

[A]

8231

4

3.7

16

64

150

200

8232

5

3.0

20

80

187

250

8233

6

2.5

24

96

225

300

8234

8

1.9

32

128

300

400

Table 14: Assignment of braking resistors

Observe the installation notes in section 3.
Dimensions and installation drawings: See section 2.8.7.

Important!

The brake resistors used must be monitored thermally by an overload protection. The
alarm contact(s) are to be integrated into the control of the drive (plant) such that the
mains voltage is switched off atthe power input of the 8230 frequency inverter, if the
contact responds. This means that the main contactor or power switch in the 3AC
supply is opened.