Technical Data

BA8230

11

Frequency accuracy for
frequency control

<0.01 %

Temperature response
of analog demand

<0.01 %/°C

Speed encoder

incremental encoder
see encoder interface option

Noise

A-weighted sound pressure level
frame size 8

<70 dB(A)

frame size 8A

<73 dB(A)

frame size 9

<72 dB(A)

frame size 9A

<74 dB(A)

Overtemperature shutdown

frame size 8 at

>95 °C

frame size 8A at

>105 °C

frame size 9 at

>105 °C

frame size 9A at

>105 °C

Ambient temperature

Operation

0 ... +55 °C

1)

Storage

-25 °C ... +65 °C

Cooling

corced air cooling
see section 2.2.3 for cooling air volumes

Coolant temperature

0 ... 40 °C at rated current, overload factor 1.2
for 60 s every 10 minutes
up to max. 55 °C with power reduction 2 % per 1 °K

0 ... 50 °C at rated current, overload factor 1.5
for 60 s every 10 minutes
up to max. 55 °C with power reduction 2 % per 1 °K

Installation altitude

1000 m above MSL, up to max. 2200 m with

power reduction 1.2 % per 100 m

Storage time

Without reforming the capacitors: 2 years, 5 months
of which at temperatures over 40°C

Protection classes
Build-in units

IP20

Cubicle-mounted units

IP21 Standard
IP31, IP43, IP54 Option

Environment class

DIN EN 60721 Part 3-3
3K3 / 3M2 / 3C2

2)

/ 2K2

- Max. relative humidity

85 % at 28 °C, condensation not permitted

- Insulation

Contamination Class II to DIN VDE 0110

Permitted switching

Precharging circuit duty cycle = 2 %/180 s,

frequency

max. 20 per hour

Power loss of control

ca. 130 W

electronics

with control board, no additional options