Electrical installation
Mains connection
5
l
101
EDK82MV371 DE/EN/FR 7.0
5
Electrical installation
Mains connection
{
Danger!
Dangerous electrical voltage
The discharge current to earth (PE) is > 3.5 mA AC or 10 mA DC.
Possible consequences:
ƒ
Death or severe injuries when touching the device in the event of an
error.
Protective measures:
ƒ
Implement the measures required in EN 61800−5−1. Especially:
–
Fixed installation
–
PE connection must comply with standards (PE conductor diameter
³ 10 mm
2
(Cu) or PE conductor must be connected twice)
Fig. 5−0
8200mot057
3.4 Nm
30 lb-in
0.5 … 0.6 Nm
4.4 … 5.3 lb-in
6mm
2.5 mm
AWG 12
2
X1
1a
X1
X1
1/N/PE AC 180V...264V 45...65Hz
2/PE AC 180V...264V 45...65Hz
L2/N
L2/N
L1
L1
PE
L1
L1
F1
F1
K1
K1
L2
N
L3
PE
X1
BR1
K14
K12
K11
BR2 L1 L2/N L3
PE
5.5 mm
K11 K12 K14
L3
Termina X1/L3 without function (application e.g. as support terminal).
X1/ BR1, BR2
Brake resistor terminals (option)