Commissioning – Lenze E82MVxxx 2Bxxx User Manual
Page 114
![background image](/manuals/566251/114/background.png)
Commissioning
Vector control
l
114
EDK82MV371 DE/EN/FR 7.0
Comment
Switch−on sequence
15.
Enter the motor data
See motor nameplate
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: Depending on the controller
Enter the value for the motor circuit
configuration (star/delta) selected!
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: Depending on the controller
Enter the value for the motor circuit
configuration (star/delta) selected!
E
Motor cos
j (C0091)
Lenze setting: Depending on the controller
16.
Start the motor parameter identification (C0148)
Only when the motor is cold!
A
Ensure that the controller is inhibited
Terminal X3/28 = LOW
B
Set C0148 = 1
Press
v
C
Enable the controller
l
Terminal X3/28 = HIGH
l
The identification starts:
– Segment
c is off
– The motor consumes current and
makes a high−pitched" tone.
– The motor does not rotate!
D
If segment
c becomes active again after approx. 30
s, inhibit controller again.
l
Terminal X3/28 = LOW
l
Identification is completed.
l
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)
l
Measured and stored:
– Motor stator resistance (C0084) =
Total resistance of motor cable
and motor
17.
If necessary, select more parameters
Activate e.g. JOG frequencies (C0037,
C0038, C0039) or motor temperature
monitoring (C0119)
18.
Go to the menu ALL
A Check the fan monitoring setting under code
C0608:
– for 8200 motec 0.25...0.37 kW and 0.55...2.2
kW:
C0608 = 0! (default setting)
– for 8200 motec 3...7.5 kW:
C0608 =1 (recommended) or C0608 = 2!
Stop!
Function must be activated during
commissioning! Otherwise, the controller may
be destroyed through overheating!
– for all other controllers:
C0608 = 0 ! (default setting)
B Select additional functions via codes, if necessary.
When all settings are complete: