Commissioning – Lenze E82MVxxx 2Bxxx User Manual

Page 120

Advertising
background image

Commissioning

Important controller codes

7

l

120

EDK82MV371 DE/EN/FR 7.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0002
*

s
uSEr

(Contin
uation)

Saving your
own basic
setting

9

PAR1

ð own basic setting

For the parameters of
the controller you can
save an own basic
setting (e.g. the delivery
status of your machine):
1. Ensure that

parameter set 1 is
active

2. Inhibit controller
3. Set C0003 = 3,

confirm with

v

4. Set C0002 = 9,

confirm with

v, the

own basic setting is
saved

5. Set C0003 = 1,

confirm with

v

6. Enable the controller

C0002
*

s
uSEr

(Contin
uation)

Loading/cop
ying the own
basic setting

By using this function
you can also just copy
PAR1 into the parameter
sets PAR2 ... PAR4

5

own basic setting

ð PAR1

Restore own basic
setting in the parameter
set selected

6

own basic setting

ð PAR2

7

own basic setting

ð PAR3

8

own basic setting

ð PAR4

C0003
*

v

Saving
parameters
non−volatilel
y

1

0

Do not save parameters in the
EEPROM

Data loss after mains
switch−off

1

Always save parameters in the
EEPROM

l

Active after every
mains connection

l

Cyclic alteration of
parameters via bus
module is not
permissible

3

Save your own basic setting in the
EEPROM

Afterwards save
parameter set 1 as own
basic setting with
C0002 = 9