Technical data

General data and operating conditions

3

l

86

EDK82MV371 DE/EN/FR 7.0

Ambient conditions

Climatic conditions

Storage

IEC/EN 60721−3−1

1K3 (−25 ... +60 °C)

Transport

IEC/EN 60721−3−2

2K3 (−25 ... +70 °C)

Operation

IEC/EN 60721−3−3

3K3 (−20 ... +60 °C)
At temperatures > +40 °C, reduce the rated output
current by 2.5 %/°C.

Site altitude

< 4000 m amsl
Reduce rated output current by 5 %/ 1000 m
above 1000 m amsl.

Electrical

Mains connection AC system

Max. mains voltage range

E82MV251... and E82MV371...

1/N/PE or 2/PE 180 V − 0 % ... 264 V + 0 %

E82MV551... to E82MV222...

3/PE 320 V − 0 % ... 550 V + 0 %

E82MV302... to E82MV752...

3/PE 320 V − 0 % ... 550 V + 0 %

Mains frequency

45 Hz − 0 % ... 65 Hz + 0 %

Mechanical

Vibration resistance
(9.81 m/s

2

= 1 g)

Germanischer
Lloyd

l

General
conditions

acceleration resistant up to 2 g

Mounting conditions

Mounting position

All mounting positions and mounting alignments are permitted

Free spacess

Above:
To the sides

100 mm
100 mm

Dimensions,

^

Chapter "Mechanical installation"

Weights

^

Chapter "Technical data", "Operation with rated power" or "Operation

with increased rated power"