Troubleshooting and fault elimination – Lenze E82MVxxx 2Bxxx User Manual
Page 135
![background image](/manuals/566251/135/background.png)
Troubleshooting and fault elimination
Fault messages
l
135
EDK82MV371 DE/EN/FR 7.0
Remedy
Cause
Fault
PC
1)
Keypad
OH3
a
53
PTC monitoring
(TRIP)
(display when
C0119 = 1 or 4)
Motor too hot due to
impermissible high currents
or frequent and too long
acceleration processes
Check drive dimensioning
No PTC connected
Connect PTC or switch off
monitoring
OH4
a
54
Controller
overtemperature
Controller is too hot inside
l
Reduce controller load
l
Improve cooling
l
Check fan in the controller
OH51
203
PTC monitoring
(display when
C0119 = 2 or 5)
Motor too hot due to
impermissible high currents
or frequent and too long
acceleration processes
Check drive dimensioning
No PTC connected
Connect PTC or switch off
monitoring
OU
c
−
DC−bus
overvoltage
(message or TRIP
configurable in
C0310)
Mains voltage is too high
Check supply voltage
OUE
a
22
Braking operation
l
Increase deceleration times
l
For operation with an
external brake resistor:
– Check dimensioning,
connection and supply
cable of the brake resistor
– Increase deceleration
times
Earth leakage at motor end
Check motor supply cable and
motor for earth fault
(disconnect motor from the
inverter)
Pr
a
75
Faulty parameter
transfer via
keypad
All parameter sets are
defective
Before enabling the controller,
repeat the data transfer or load
the Lenze setting
Pr1
a
72
Faulty PAR1
transfer via
keypad
Parameter set 1 is defective
Pr2
a
73
Faulty PAR2
transfer via
keypad
Parameter set 2 is defective
Pr3
a
77
Faulty PAR3
transfer via
keypad
Parameter set 3 is defective
Pr4
a
78
Faulty PAR4
transfer via
keypad
Parameter set 4 is defective