Mechanical installation

Motor mounting

4

l

99

EDK82MV371 DE/EN/FR 7.0

Motor connection

{

Danger!

ƒ

All control terminals only have basic insulation (single isolating distance)
after connecting a PTC thermistor or a thermal contact.

ƒ

Protection against accidental contact in case of a defective isolating
distance is only guaranteed through external measures, e. g. double
insulation.

}

Danger!

The connection between terminal X2 and sheet must not be released!

Fig. 4−4

8200mot055

101

0.5...0.6 Nm
4.4…5.3 lb-in

T2

W V

U

T1

PE T2 T1

J >

X2

6mm

2.5 mm

AWG 12

2

5.5 mm

PE

U1 V1 W1 PE

W2

V2

U2

X2

1a

3.4 Nm
30 lb-in

!

5.5 mm

X2/ T1,T2 Terminals of motor temperature monitoring with PTC thermistor (PTC) or thermal contact

(NC contact).
Activate motor temperature monitoring with C0119 (e.g. C0119 = 1)!