Mechanical installation
motec with motor or geared motor
l
91
EDK82MV371 DE/EN/FR 7.0
EMC−compliant wiring
Conditions for trouble−free operation:
ƒ Except for the mains cable, use shielded cables only.
ƒ Carefully connect the shielding to PE.
ƒ Connect motor and mains PE conductors to separate PE terminals.
A
E
B
X1
C
8200mot151
D
F
Shield connection:
1. Prepare the cable
2. Insert the cable tie
3. Lay the cable into the
cable tie and tighten it.
The shield must be
tightly connected to
the shield sheet.
0
Mains cable L1, N, PE or. L1, L2, PE
1
PE connection for mains cable
2
PE connection for motor
3
Shielded control cable
4
Shield connection, control cables; fix the shield tightly to the sheet with the cable tie
5
Function module
X1
Terminal strip mains connection
PES
HF−shield termination by large surface connection to PE