Commissioning – Lenze E82MVxxx 2Bxxx User Manual
Page 126
![background image](/manuals/566251/126/background.png)
Commissioning
Important controller codes
l
126
EDK82MV371 DE/EN/FR 7.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0087 Rated motor
speed
à
300
{1 rpm}
16000
à
Device−dependent
C0088 Rated motor
current
à
0.0
0.1 (A)
650.0
à
Device−dependent
0.0 ... 2.0 x rated output
current of the controller
C0089 Rated motor
frequency
50
10
{1 Hz}
960
C0090 Rated motor
voltage
à
50
{1 V}
500
à
230 V for 230 V
controllers,
400 V for 400 V
controllers
C0091 Motor cos
а
0.40
{0.1}
1.0
а
Device−dependent
C0119
v
Configuratio
n of motor
temperature
monitoring
(PTC input) /
earth fault
detection
0
0
PTC input
inactive
Earth fault
detection active
l
Configure signal
output in C0415
l
If several parameter
sets are used,
monitoring has to be
set separately for
every parameter set.
l
Deactivate earth fault
detection if the earth
fault detection is
actuated
unintentionally.
l
If the earth fault
detection is activated,
the motor starts with
a delay of approx.
40 ms after controller
enable has been set.
1
PTC input active,
TRIP effected
2
PTC input active,
warning effected
3
PTC input
inactive
Earth fault
detection inactive
4
PTC input active,
TRIP effected
5
PTC input active,
warning effected
C0140
*
Additive
frequency
setpoint
(NSET1−NAD
D)
0.00
−650.00
{0.02
Hz}
650.00
l
Selection via
j
function of the
keypad or parameter
channel
l
Acts additively on the
main setpoint
l
Value will be stored
when switching the
mains or removing
the keypad
l
C0140 is only
transferred during
parameter set
transfer with GDC
(not with keypad)