Commissioning – Lenze E82MVxxx 2Bxxx User Manual

Page 126

Advertising
background image

Commissioning

Important controller codes

7

l

126

EDK82MV371 DE/EN/FR 7.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0087 Rated motor

speed

à

300

{1 rpm}

16000

à

Device−dependent

C0088 Rated motor

current

à

0.0

0.1 (A)

650.0

à

Device−dependent

0.0 ... 2.0 x rated output
current of the controller

C0089 Rated motor

frequency

50

10

{1 Hz}

960

C0090 Rated motor

voltage

à

50

{1 V}

500

à

230 V for 230 V
controllers,
400 V for 400 V
controllers

C0091 Motor cos

а

0.40

{0.1}

1.0

а

Device−dependent

C0119

v

Configuratio
n of motor
temperature
monitoring
(PTC input) /
earth fault
detection

0

0

PTC input
inactive

Earth fault
detection active

l

Configure signal
output in C0415

l

If several parameter
sets are used,
monitoring has to be
set separately for
every parameter set.

l

Deactivate earth fault
detection if the earth
fault detection is
actuated
unintentionally.

l

If the earth fault
detection is activated,
the motor starts with
a delay of approx.
40 ms after controller
enable has been set.

1

PTC input active,
TRIP effected

2

PTC input active,
warning effected

3

PTC input
inactive

Earth fault
detection inactive

4

PTC input active,
TRIP effected

5

PTC input active,
warning effected

C0140
*

Additive
frequency
setpoint
(NSET1−NAD
D)

0.00

−650.00

{0.02

Hz}

650.00

l

Selection via

j

function of the
keypad or parameter
channel

l

Acts additively on the
main setpoint

l

Value will be stored
when switching the
mains or removing
the keypad

l

C0140 is only
transferred during
parameter set
transfer with GDC
(not with keypad)