Commissioning – Lenze E82MVxxx 2Bxxx User Manual
Page 128
Commissioning
Important controller codes
l
128
EDK82MV371 DE/EN/FR 7.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0517
*
v
User menu
l
After mains
switching or in the
g function the code
from C0517/1 is
displayed.
l
In the Lenze setting
the user menu
contains the most
important codes for
commissioning the
operating mode "V/f
characteristic control
with a linear
characteristic"
l
If the password
protection is active,
only the codes
entered in C0517 can
be freely accessed
l
If less than 10 codes
are required, assign
the value "0" (zero) to
the memory locations
not used. Please
observe that the
software
automatically assigns
code C0050 to a
memory location that
is not used, if it has
not been explicitly
assigned to another
memory location.
1 Memory 1
50
C0050 Output frequency (MCTRL1−NOUT)
2 Memory 2
34
C0034 Range of analog setpoint selection
3 Memory 3
7
C0007 Fixed configuration of digital input
signals
4 Memory 4
10
C0010 Minimum output frequency
5 Memory 5
11
C0011 Maximum output frequency
6 Memory 6
12
C0012 Acceleration time main setpoint
7 Memory 7
13
C0013 Deceleration time main setpoint
8 Memory 8
15
C0015 V/f rated frequency
9 Memory 9
16
C0016 V
min
boost
10 Memory 10
2
C0002 Parameter set transfer
Possible entries for C0517
xxxx
All codes apart from the codes
labelled with "(A)".
Syntax:
Codes: C0517/x = cccc
Subcodes: C0517/x =
cccc.ss
C0608
*
Fan
monitoring
0
0
Inactive
8200 motec 3 ... 7.5 kW:
Function must be
activated during
commissioning
(recommended: C0608 =
1)! Otherwise, the
controller may be
destroyed due to
overheating.
For all other controllers:
It is essential to set
C0608 = 0.
1
TRIP error message
2
Warning