Fuses and cable cross-sections, Dimensioning of mains contactors, Fuses and cable cross−sections – Lenze E82MVxxx 2Bxxx User Manual

Page 102: Electrical installation

Advertising
background image

Electrical installation

Mains connection

5

l

102

EDK82MV371 DE/EN/FR 7.0

Fuses and cable cross−sections

Type

Mains

Installation acc. to EN 60204−1

FI

1)

Fuse

Circuit breaker

L1, L2, N, PE

[mm

2

]

E82MV251_2B
E82MV371_2B

2/PE AC or
1/N/PE AC
180 ... 264 V;
45 ... 65 Hz

M10 A

C10 A

1.5

³ 30 mA

1)

Pulse current sensitive or universal−current sensitive earth−leakage circuit breaker

Observe national and regional regulations

If using earth−leakage circuit breakers, observe the following:

ƒ Only install the earth−leakage circuit breaker between supplying mains and drive

controller.

ƒ Earth−leakage circuit breakers can trip incorrectly due to

– capacitive compensation currents flowing in the cable shields during operation

(particularly with long, shielded motor cables),

– simultaneous connection of several controllers to the mains supply.

Dimensioning of mains contactors

Type

Rated current of mains contactor

With starting current limitation

1)

Without starting current limitation

E82MV251_2B

10 A

20 A

E82MV371_2B

Observe national and regional regulations

1)

e.g. current limiting module E82ZJ004