Commissioning
Important controller codes
l
127
EDK82MV371 DE/EN/FR 7.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0148
*
s
Identifying
motor data
0
0
Ready
Only when the motor is
cold!
1. Inhibit controller,
wait until drive is at
standstill
2. Enter the correct
values from the
motor nameplate in
C0087, C0088, C0089,
C0090, C0091
3. Set C0148 = 1,
confirm with
v
4. Enable controller:
The identification
– starts,
c goes
out
– the motor
"whistles" faintly
but it does not
rotate!
– takes approx. 30 s
– is completed when
c is lit again
5. Inhibit controller
1
Start identification
l
V/f rated frequency (C0015), slip
compensation (C0021) and motor
stator inductance (C0092) are
calculated and saved
l
The motor stator resistance
(C0084) = total resistance of the
motor cable and motor is
measured and saved