Commissioning, User – Lenze E82MVxxx 2Bxxx User Manual
Page 124
![background image](/manuals/566251/124/background.png)
Commissioning
Important controller codes
l
124
EDK82MV371 DE/EN/FR 7.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0012
uSEr
Acceleration
time main
setpoint
5.00
0.00
{0.02 s}
1300.00 Reference: frequency
change 0 Hz ... C0011
l
Additional setpoint
ðC0220
l
Acceleration times
that can be activated
via digital signals
ð
C0101
C0013
uSEr
Deceleration
time main
setpoint
5.00
0.00
{0.02 s}
1300.00 Reference: frequency
change C0011... 0 Hz
l
Additional setpoint
ðC0221
l
Deceleration times
that can be activated
via digital signals
ð
C0103
C0014
v
Operating
mode
2
2
V/f characteristic control V ~ f
(linear characteristic with constant
V
min
boost)
l
Commissioning is
possible without
identifying motor
parameters
l
Advantage of
identification with
C0148:
– Improved smooth
running at low
speeds
– V/f rated
frequency (C0015)
and slip (C0021)
are calculated and
saved. They do not
have to be entered
3
V/f characteristic control V ~ f
2
(square−law characteristic with
constant V
min
boost)
4
Vector control
In the case of the first
selection enter the
motor data and identify
them with C0148
Otherwise
commissioning is not
possible
When C0014 = 5, C0019
must be set = 0
(automatic DC injection
brake is deactivated)
5
Sensorless torque control with speed
limitation
l
Torque setpoint via C0412/6
l
Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum
frequency (C0011)
C0015
uSEr
V/f rated
frequency
50.00 7.50
{0.02
Hz}
960.00
l
C0015 is calculated
and saved during the
motor parameter
identification with
C0148.
l
The setting applies to
all permitted mains
voltages