Commissioning, User – Lenze E82MVxxx 2Bxxx User Manual

Page 124

Advertising
background image

Commissioning

Important controller codes

7

l

124

EDK82MV371 DE/EN/FR 7.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0012

uSEr

Acceleration
time main
setpoint

5.00

0.00

{0.02 s}

1300.00 Reference: frequency

change 0 Hz ... C0011

l

Additional setpoint

ðC0220

l

Acceleration times
that can be activated
via digital signals

ð

C0101

C0013

uSEr

Deceleration
time main
setpoint

5.00

0.00

{0.02 s}

1300.00 Reference: frequency

change C0011... 0 Hz

l

Additional setpoint

ðC0221

l

Deceleration times
that can be activated
via digital signals

ð

C0103

C0014

v

Operating
mode

2

2

V/f characteristic control V ~ f
(linear characteristic with constant
V

min

boost)

l

Commissioning is
possible without
identifying motor
parameters

l

Advantage of
identification with
C0148:
– Improved smooth

running at low
speeds

– V/f rated

frequency (C0015)
and slip (C0021)
are calculated and
saved. They do not
have to be entered

3

V/f characteristic control V ~ f

2

(square−law characteristic with
constant V

min

boost)

4

Vector control

In the case of the first
selection enter the
motor data and identify
them with C0148
Otherwise
commissioning is not
possible
When C0014 = 5, C0019
must be set = 0
(automatic DC injection
brake is deactivated)

5

Sensorless torque control with speed
limitation

l

Torque setpoint via C0412/6

l

Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum
frequency (C0011)

C0015

uSEr

V/f rated
frequency

50.00 7.50

{0.02

Hz}

960.00

l

C0015 is calculated
and saved during the
motor parameter
identification with
C0148.

l

The setting applies to
all permitted mains
voltages