background image

Troubleshooting and fault elimination

Troubleshooting

8

l

129

EDK82MV371 DE/EN/FR 7.0

8

Troubleshooting and fault elimination

Troubleshooting

Maloperation

Cause

Remedy

Motor does not rotate

DC−bus voltage too low
(red LED is blinking every 0.4 s;
keypad displays: LU)

Check mains voltage

Controller inhibited
(Green LED is blinking, keypad display:

c)

Deactivate controller inhibit,
controller inhibit can be set
via several sources

Automatic start inhibited (C0142 = 0
or 2)

LOW−HIGH edge at X3/28
If necessary, correct starting
condition (C0142)

DC−injection braking (DCB) active

Deactivate DC injection brake

Mechanical motor brake is not
released

Manual or electrical release of
mechanical motor brake

Quick stop (QSP) active (keypad
display:

c)

Deactivate quick stop

Setpoint = 0

Select setpoint

JOG setpoint activated and JOG
frequency = 0

Select JOG setpoint
(C0037 ... C0039)

Fault active

Eliminate fault

Incorrect parameter set active

Change to correct parameter
set via terminal

Operating mode C0014 = −4−, −5− set,
but no motor parameter identification

Identify motor parameters
(C0148)

Assignment of several functions
excluding each other to one signal
source in C0410

Correct configuration in
C0410

Use of internal voltage source X3/20
for the function modules Standard
I/O, INTERBUS, PROFIBUS−DP, or
LECOM−B (RS485):
No jumper between X3/7 and X3/39

Jumper terminals

Motor does not rotate smoothly

Motor cable defective

Check motor cable

Maximum current set too low (C0022,
C0023)

Adjust settings to the
application

Motor is under− or overexcited

Check parameter setting
(C0015, C0016, C0014)

C0084, C0087, C0088, C0089, C0090,
C0091 and/or C0092 not adjusted to
the motor data

Adjust codes manually or
identify motor parameters
(C0148); optimise vector
control

Current consumption of motor
too high

Setting of C0016 too high

Correct setting

Setting of C0015 too low

Correct setting

C0084, C0087, C0088, C0089, C0090,
C0091 and/or C0092 not adjusted to
the motor data

Adjust codes manually or
identify motor parameters
(C0148); optimise vector
control

Advertising