Troubleshooting and fault elimination – Lenze E82MVxxx 2Bxxx User Manual
Page 132
![background image](/manuals/566251/132/background.png)
Troubleshooting and fault elimination
Fault messages
l
132
EDK82MV371 DE/EN/FR 7.0
Keypad
PC
1)
Fault
Cause
Remedy
noer
0
No fault
−
−
ccr
a
71
System fault
Strong interference
injections on the control
cables
Shield control cables
Earth loops in the wiring
ce0
a
61
Communication
error on AIF
(configurable in
C0126)
Faulty transmission of
control commands via AIF
Insert the communication
module firmly into the diagnosis
terminal
ce1
a
62
Communication
error on CAN−IN1
with sync control
CAN−IN1 object receives
faulty data, or
communication is
interrupted
l
Check plug connection bus
module
ó FIF
l
Check transmitter
l
Increase monitoring time in
C0357/1, if necessary
ce2
a
63
Communication
error on CAN−IN2
CAN−IN2 object receives
faulty data, or
communication is
interrupted
l
Check plug connection bus
module
ó FIF
l
Check transmitter
l
Increase monitoring time in
C0357/2, if necessary
ce3
a
64
Communication
error on CAN−IN1
with event or
time control
CAN−IN1 object receives
faulty data, or
communication is
interrupted
l
Check plug connection bus
module
ó FIF
l
Check transmitter
l
Increase monitoring time in
C0357/3, if necessary
ce4
a
65
BUS−OFF
(many
communication
errors occurred)
Controller has received too
many faulty telegrams via
the system bus and has been
disconnected from the bus
l
Check bus termination
l
Check shield connection of
the cables
l
Check PE connection
l
Check bus load, reduce the
baud rate, if necessary
ce5
a
66
CAN time−out
(configurable in
C0126)
For remote
parameterisation via the
system bus (C0370):
Slave does not respond.
Communication monitoring
time has been exceeded
l
Check wiring of the system
bus
l
Check system bus
configuration
For operation with
application I/O:
Parameter set change−over
has been parameterised
incorrectly
The "parameter set
change−over" signal (C0410/13,
C0410/14) must be connected
to the same source in all
parameter sets
For operation with module
on FIF:
Internal error
Contact Lenze