Commissioning – Lenze E82MVxxx 2Bxxx User Manual

Page 125

Advertising
background image

Commissioning

Important controller codes

7

l

125

EDK82MV371 DE/EN/FR 7.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0016

uSEr

V

min

boost

а

0.00

{0.01 %}

40.00

а

device−dependent

Setting applies to all
permitted mains
voltages

C0034
*

v
uSEr

Range of
setpoint
selection
Standard I/O
(X3/8)

Observe switch position
of the function module!

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA

1

Current 4 ... 20 mA

Reversal of rotation
direction only possible
with a digital signal.

2

Bipolar voltage −10 V ... +10 V

l

Minimum output
frequency (C0010)
not effective

l

Individually adjust
offset and gain

3

Current 4 ... 20 mA open−circuit
monitored

TRIP Sd5 if I < 4 mA
Reversal of rotation
direction only possible
with a digital signal.

C0034
*

v

(A)

uSEr

Range of
setpoint
selection
Application
I/O

Observe jumper position
of the function module!

1 X3/1U, X3/1I

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10 V

2 X3/2U, X3/2I

1

Bipolar voltage −10 V ... +10 V

Minimum output
frequency (C0010) not
effective

2

Current 0 ... 20 mA

3

Current 4 ... 20 mA

Reversal of rotation
direction only possible
with a digital signal.

4

Current 4 ... 20 mA open−circuit
monitored

Reversal of rotation
direction only possible
with a digital signal.
TRIP Sd5 at I < 4 mA

C0037 JOG1

20.00 −650.00

{0.02

Hz}

650.00 JOG = fixed setpoint

Additional fixed
setpoints

ðC0440

C0038 JOG2

30.00 −650.00

{0.02

Hz}

650.00

C0039 JOG3

40.00 −650.00

{0.02

Hz}

650.00

C0050
*

uSEr

Output
frequency
(MCTRL1−NO
UT)

−650.00

{Hz}

650.00 Read only: Output

frequency without slip
compensation