Commissioning
Important controller codes
l
125
EDK82MV371 DE/EN/FR 7.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0016
uSEr
V
min
boost
а
0.00
{0.01 %}
40.00
а
device−dependent
Setting applies to all
permitted mains
voltages
C0034
*
v
uSEr
Range of
setpoint
selection
Standard I/O
(X3/8)
Observe switch position
of the function module!
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1
Current 4 ... 20 mA
Reversal of rotation
direction only possible
with a digital signal.
2
Bipolar voltage −10 V ... +10 V
l
Minimum output
frequency (C0010)
not effective
l
Individually adjust
offset and gain
3
Current 4 ... 20 mA open−circuit
monitored
TRIP Sd5 if I < 4 mA
Reversal of rotation
direction only possible
with a digital signal.
C0034
*
v
(A)
uSEr
Range of
setpoint
selection
Application
I/O
Observe jumper position
of the function module!
1 X3/1U, X3/1I
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
2 X3/2U, X3/2I
1
Bipolar voltage −10 V ... +10 V
Minimum output
frequency (C0010) not
effective
2
Current 0 ... 20 mA
3
Current 4 ... 20 mA
Reversal of rotation
direction only possible
with a digital signal.
4
Current 4 ... 20 mA open−circuit
monitored
Reversal of rotation
direction only possible
with a digital signal.
TRIP Sd5 at I < 4 mA
C0037 JOG1
20.00 −650.00
{0.02
Hz}
650.00 JOG = fixed setpoint
Additional fixed
setpoints
ðC0440
C0038 JOG2
30.00 −650.00
{0.02
Hz}
650.00
C0039 JOG3
40.00 −650.00
{0.02
Hz}
650.00
C0050
*
uSEr
Output
frequency
(MCTRL1−NO
UT)
−650.00
{Hz}
650.00 Read only: Output
frequency without slip
compensation