Mechanical installation

Wall mounting

4

l

94

EDK82MV371 DE/EN/FR 7.0

Wiring on the motor side

{

Danger!

ƒ

All control terminals only have basic insulation (single isolating distance)
after connecting a PTC thermistor or a thermal contact.

ƒ

Protection against accidental contact in case of a defective isolating
distance is only guaranteed through external measures, e. g. double
insulation.

}

Danger!

The connection between terminal X2 and sheet must not be released!

8200mot052

0.5...0.6 Nm
4.4…5.3 lb-in

T2

W V

U

T1

PE T2 T1

J >

X2

6mm

2.5 mm

AWG 12

2

5.5 mm

PE

X2

1a

A

B

3.4 Nm
30 lb-in

!

5.5 mm

0

Use low−capacitance motor cable! (core/core

£ 75 pF/m, core/shield £ 150 pF/m)

A motor cable that is as short as possible has a positive effect on the drive behaviour!
Cable cross−sections U, V, W, PE:

E82MV251_2B

®

1 mm

2

(AWG 18),

shielded

E82MV371_2B

®

1 mm

2

(AWG 18),

shielded

1

Install a separate cable (shielded) to X2/T1 and X2/T2 for the motor temperature monitoring.

Install control cables and mains cables with a spatial separation from the motor cable!