Commissioning
Linear V/f−characteristic control
l
112
EDK82MV371 DE/EN/FR 7.0
Comment
Switch−on sequence
14.
If you want to change the settings, go to the ALL
menu
For instance activate JOG frequencies
(C0037, C0038, C0039) or motor
temperature monitoring (C0119)
15.
Go to the menu ALL
A Check the fan monitoring setting under code
C0608:
– for 8200 motec 0.25...0.37 kW and 0.55...2.2
kW:
C0608 = 0! (default setting)
– for 8200 motec 3...7.5 kW:
C0608 =1 (recommended) or C0608 = 2!
Stop!
Function must be activated during
commissioning! Otherwise, the controller may
be destroyed through overheating!
– for all other controllers:
C0608 = 0 ! (default setting)
B Select additional functions via codes, if necessary.
When all settings are complete:
16.
Select setpoint
E.g. via potentiometer at
terminals 7, 8, 9
17.
Enable the controller
Terminal X3/28 = HIGH
18.
The drive is now running.
If the drive does not start, additionally
press
u