Commissioning – Lenze E82MVxxx 2Bxxx User Manual

Page 112

Advertising
background image

Commissioning

Linear V/f−characteristic control

7

l

112

EDK82MV371 DE/EN/FR 7.0

Comment

Switch−on sequence

14.

If you want to change the settings, go to the ALL
menu

For instance activate JOG frequencies
(C0037, C0038, C0039) or motor
temperature monitoring (C0119)

15.

Go to the menu ALL
A Check the fan monitoring setting under code

C0608:
– for 8200 motec 0.25...0.37 kW and 0.55...2.2

kW:
C0608 = 0! (default setting)

– for 8200 motec 3...7.5 kW:

C0608 =1 (recommended) or C0608 = 2!
Stop!
Function must be activated during
commissioning! Otherwise, the controller may
be destroyed through overheating!

– for all other controllers:

C0608 = 0 ! (default setting)

B Select additional functions via codes, if necessary.

When all settings are complete:

16.

Select setpoint

E.g. via potentiometer at
terminals 7, 8, 9

17.

Enable the controller

Terminal X3/28 = HIGH

18.

The drive is now running.

If the drive does not start, additionally
press

u