Troubleshooting and fault elimination

Fault messages

8

l

133

EDK82MV371 DE/EN/FR 7.0

Remedy

Cause

Fault

PC

1)

Keypad

ce6

a

67

System bus
(CAN) function
module on FIF
has the
"Warning" or
"BUS−OFF"
status
(configurable in
C0126)

CAN controller reports
"Warning" or "BUS−OFF"
status

l

Check bus termination

l

Check shield connection of
the cables

l

Check PE connection

l

Check bus load, reduce the
baud rate, if necessary

ce7

a

68

Communication
error during
remote
parameterisatio
n via system bus
(C0370)
(configurable in
C0126)

Node does not respond or is
not available

l

Check bus termination

l

Check shield connection of
the cables

l

Check PE connection

l

Check bus load, reduce the
baud rate, if necessary

For operation with
application I/O:
Parameter set change−over
has been parameterised
incorrectly

The "parameter set
change−over" signal (C0410/13,
C0410/14) must be connected
to the same source in all
paramerter sets

EEr

a

91

External fault
(TRIP−SET)

A digital signal assigned to
the TRIP−Set function is
activated

Check external encoder

ErP0
...
ErP19

a

Communication
abort between
keypad and
standard device

Various

Contact Lenze

FAn1

a

95

Fan failure
(only 8200
motec
3 ... 7.5 kW)
TRIP or warning
configurable in
C0608

Fan is defective

Replace fan

FAn1

Fan is not connected

Connect fan
Check wiring

H05

a

105

Internal fault

Contact Lenze

id1

a

140

Faulty parameter
identification

Motor is not connected

Connect motor

LP1

a

32

Motor phase
error
(display when
C0597 = 1)

l

Failure of one/several
motor phases

l

Motor current is too low

l

Check motor supply cables

l

Check V

min

boost,

l

Connect motor with a
corresponding power or
adapt motor with C0599

LP1

182

Motor phase
error
(Display when
C0597 = 2)